#  CHECK SYSTEM STATUS
#

[docs]def is_mechanical_ventilation_active(bpr, tsd, t): # TODO: check for ventilation schedule if has_mechanical_ventilation(bpr) \ and tsd['m_ve_required'][t] > 0: # mechanical ventilation is active if there is a ventilation demand return True elif has_mechanical_ventilation(bpr) \ and is_night_flushing_active(bpr, tsd, t): # mechanical ventilation for night flushing return True else: return False
[docs]def is_window_ventilation_active(bpr, tsd, t): if has_window_ventilation(bpr) \ and not is_mechanical_ventilation_active(bpr, tsd, t): # window ventilation in case of non-active mechanical ventilation return True else: return False
[docs]def is_mechanical_ventilation_heat_recovery_active(bpr, tsd, t): """ Control of activity of heat exchanger of mechanical ventilation system Author: Gabriel Happle Date: APR 2017 :param bpr: Building Properties :type bpr: BuildingPropertiesRow :param tsd: Time series data of building :type tsd: dict :param t: time step / hour of the year :type t: int :return: Heat exchanger ON/OFF status :rtype: bool """ if is_mechanical_ventilation_active(bpr, tsd, t)\ and has_mechanical_ventilation_heat_recovery(bpr)\ and helpers.is_heatingseason_hoy(t): # heat recovery is always active if mechanical ventilation is active (no intelligent by pass) # this is the usual system configuration according to Clayton Miller return True elif is_mechanical_ventilation_active(bpr, tsd, t)\ and has_mechanical_ventilation_heat_recovery(bpr)\ and helpers.is_coolingseason_hoy(t)\ and tsd['theta_a'][t-1] < tsd['T_ext'][t]: return True elif is_mechanical_ventilation_active(bpr, tsd, t) \ and helpers.is_coolingseason_hoy(t) \ and tsd['theta_a'][t-1] >= tsd['T_ext'][t]: # heat recovery is deactivated in the cooling case, # if outdoor air conditions are colder than indoor (free cooling) return False else: return False
[docs]def is_night_flushing_active(bpr, tsd, t): # night flushing is available for window ventilation (manual) and mechanical ventilation (automatic) # night flushing is active during the night in the cooling season, # IF the outdoor conditions are favourable (only temperature at the moment) temperature_zone_control = 26 # (°C) night flushing only if temperature is higher than 26 # TODO review and make dynamic delta_t = 2 # (°C) night flushing only if outdoor temperature is two degrees lower than indoor # TODO review and make dynamic if has_night_flushing(bpr) \ and helpers.is_coolingseason_hoy(t) \ and helpers.is_nighttime_hoy(t) \ and tsd['theta_a'][t-1] > temperature_zone_control \ and tsd['theta_a'][t-1] > tsd['T_ext'][t] + delta_t: return True else: return False
[docs]def is_economizer_active(bpr, tsd, t): """ Control of activity of economizer of mechanical ventilation system Economizer of mechanical ventilation is controlled via zone set point temperatures, indoor air temperature and outdoor air temperature. Economizer is active during cooling season if the indoor air temperature exceeds the set point and the outdoor temperatures are lower than the set point. Economizer increases mechanical ventilation flow rate to the maximum. Author: Gabriel Happle Date: APR 2017 :param bpr: Building Properties :type bpr: BuildingPropertiesRow :param tsd: Time series data of building :type tsd: dict :param t: time step / hour of the year :type t: int :return: Economizer ON/OFF status :rtype: bool """ if has_mechanical_ventilation_economizer(bpr) \ and helpers.is_coolingseason_hoy(t) \ and tsd['theta_a'][t-1] > tsd['ta_cs_set'][t] >= tsd['T_ext'][t]: return True else: return False
# # CHECK SYSTEM CONFIGURATION #
[docs]def has_mechanical_ventilation(bpr): if bpr.hvac['MECH_VENT']: return True elif not bpr.hvac['MECH_VENT']: return False else: raise ValueError(bpr.hvac['MECH_VENT'])
[docs]def has_window_ventilation(bpr): if bpr.hvac['WIN_VENT']: return True elif not bpr.hvac['WIN_VENT']: return False else: raise ValueError(bpr.hvac['WIN_VENT'])
[docs]def has_mechanical_ventilation_heat_recovery(bpr): if bpr.hvac['HEAT_REC']: return True elif not bpr.hvac['HEAT_REC']: return False else: raise ValueError(bpr.hvac['HEAT_REC'])
[docs]def has_night_flushing(bpr): if bpr.hvac['NIGHT_FLSH']: return True elif not bpr.hvac['NIGHT_FLSH']: return False else: raise ValueError(bpr.hvac['NIGHT_FLSH'])
[docs]def has_mechanical_ventilation_economizer(bpr): if bpr.hvac['ECONOMIZER']: return True elif not bpr.hvac['ECONOMIZER']: return False else: raise ValueError(bpr.hvac['ECONOMIZER'])